        2. Hello! Welcome to Jiangsu Zhongwei Measurement and Control Instrument Co., Ltd.

          Liquid vortex flowmeter

          5液(ye)體(ti)渦(wo)街流量(liang)計.png
          • 5液(ye)體(ti)渦街流(liu)量計(ji).png
          Liquid vortex flowmeter is a kind of new flow meter has the international advanced level.Because it …

          Description:

          Products overview:
          ZW - LUGB seriesLiquid vortex flowmeterIs using the liquid vibration principle and development of a new type of flowmeter, widely used in petroleum, chemical industry, metallurgy, paper and other fluid measurement.The flowmeter have no moving parts, high reliability, high precision, long life, can be in a very wide range of flow measuring precise instantaneous flow and cumulative flow of liquid.It is not affected by medium, the influence of temperature, pressure, viscosity and component without plugging, BuKa, not easy to scale formation, corrosion resistance, high temperature, high pressure safety explosion-proof, suitable for bad environment.Traffic integration of scoring display and remote transmission, and can output pulse signals or electric current signal and computer networking.

          Second, the working principle:
          ZW - LUGB seriesLiquid vortex flowmeter is by the design in the flow field in the vortex body, detection probe and the corresponding electronic circuit, etc.When the fluid flows through the spiral body occurs, it is formed on both sides of the two rows of vortex variations, this vortex is known as the karman vortex street.Stern, on the basis of the theory of karman vortex street Hal and puts forward the karman vortex street frequency is proportional to the velocity of the fluid, the relation between the frequency and velocity are presented:
          F = St * V/d type:
          F vortex frequency (Hz)
          V vortex occurred body on both sides of the average flow velocity (m/s)
          St, luo hall coefficient (constant)
          These variations of vortex is formed a series of variations of negative pressure, the pressure on detecting probe, and produce a series of alternating electric signals, after dealing with the preamplifier conversion, plastic, amplification, the output is proportional to the vortex synchronous pulse frequency signal (or standard).
          Applications:
          ZW - LUGB seriesLiquid vortex flow meter according to the principle of Carmen (karman vortex street measuring gas volume flow of liquid, steam or, standard condition or volume flow to mass flow volume flow.Widely used in various industries of gas, liquid and steam flow measurement, can also be measured turbid liquid containing small makings, impurities, and can be used as flow transmitter used in automatic control system.
          Four, the main features:
          1, can measure the steam, gas, liquid and the volume flow to mass flow.
          2, dismantling the can realize does not block the flow sensor, which can realize the amplifier and sensor separation (separation distance of 15 m).
          3, USES the interference elimination circuit and anti vibration sensing head, make the instrument has certain environmental vibration resistance.
          4, small pressure loss, wide range, range of 10 to 40 times.
          5, no mechanical moving parts, long-term stability and simple structure is convenient for installation and maintenance.
          6, measurable medium temperature up to + 350 ℃ (+ 450 ℃).
          Five, the technical parameters:
          Measuring medium: liquid, gas, natural gas, steam (saturated steam and superheated steam);
          Measuring range: the Reynolds number is 5 x 103 ~ 7 x 106
          Normal measuring range: Reynolds number is 2 x 104 ~ 7 x 106
          Measuring velocity range: liquid 0.5 ~ 7 m/s gas 4 ~ 35 mm/s steam 7 ~ 70 m/s
          By measurement of body temperature: - 40 ℃ ~ + 300 ℃
          By measurement of body temperature: 1.6, 4, 25 mpa
          Accuracy: level 1, 1.5, 0.5 (by nonlinear dressing can reach 0.5);
          Repeatability: 0.2% of the indicated value;
          The table body material: ICr18Ni9Ti;
          Pressure loss: delta (r = 1.2 * 10-6 V2 type: delta r - P - pressure loss measured the fluid density (Kg/m3) v - tube average flow velocity (m/s) ambient temperature: - 20 ℃ ~ + 55 ℃ (special request order)
          Environmental humidity: 90% RH or less
          The atmospheric pressure: 86-106 kpa
          External power source: 3.6 ~ 224 VDC
          Power source: within 3 ~ 4.5 VVDDC
          Working power supply: 80 / A
          Operating voltage: 2.7 ~ 3.6 v
          Operating frequency: 0.1 ~ 3000 h
          Signal remote transmission distance: 100 mm
          Signal output: pulse output (power source) 4 ~ 20 madc output current (two wire system for 24 VDC power supply) pulse output and the output current can only choose one way.

          Six, appearance size:

          DN

          A

          B

          C

          D

          15

          90

          Φ 57

          383

          45

          20

          100

          Φ 57

          388

          50

          25

          100

          Φ 57

          394

          50

          32

          100

          Φ 65

          396

          50

          40

          100

          Φ 75

          401

          50

          50

          110

          Φ 87

          407

          55

          65

          110

          Φ 109

          418

          55

          80

          110

          Φ 120

          423

          55

          100

          120

          Φ 149

          447

          60

          125

          125

          Φ 175

          474

          65

          150

          145

          Φ 203

          501

          75

          200

          170

          Φ 259

          556

          100

          250

          190

          Φ 312

          608

          120

          300

          210

          Φ 363

          660

          140

          350

          230

          Φ 409

          709

          160

          400

          250

          Φ 460

          756

          180

          450

          275

          Φ 520

          814

          205

          500

          290

          Φ 575

          869

          225

          Seven, pipe requirements:
          1, the requirement for straight pipe:
          In order to ensure that the instrument, accurate to run normally, sensor must have a certain straight pipe upstream and downstream of the installation points, to adjust the flow field, as shown.

          Figure 1: concentric contraction tube;
          Figure 2: the concentric expansion tube;
          Figure 3: a 90 - degree Angle;
          Figure 4: the same plane of two 90 - degree Angle;
          Figure 5: different plane of two 90 - degree Angle;
          Figure 6: regulating valve should be installed downstream of the sensor in 5 d to the distance, if the sensor must be installed in the upstream, the sensors should be not less than 50 d upstream, straight pipe section downstream straight pipe section should be not less than 5 d.
          2, the requirement of pipe:
          A, upstream and downstream piping diameter D and the same as the sensor inner diameter DN, its difference satisfy the following conditions: 0.95 DN D 1.1 or less or less DN.
          B, piping shall be concentric with sensor, coaxial degree should be less than 0.05 DN.
          C, gasket not protruding into the pipe, the inner diameter slightly larger than sensors.
          D, if you want to stop inspection and cleaning the sensor, the by-pass pipe should be set up,As shown in the figure below.

           
          3, the requirement of pipe vibration:
          Sensors to avoid installed on the strong pipeline vibration, if necessary to install, shock absorption measures must be taken, respectively at the upstream and downstream of sensor 2 d piping fastening device, and vibration-proof pad.
          Special note: in the air compressor exit strong vibration, cannot install the sensors, shall be installed after the gas storage.
          4, demand for air condition:
          A, the gas to be tested for single phase pipe flow, continuously flowing through a pipe.
          Before b, the gas flows through the flowmeter, the flow rate must be parallel to the pipe axis, can not have vortex flow.
          C, flow should be a subsonic, a pulse, its flow change slowly over time.
          5, the flowmeter installation requirements:
          Vortex street flowmeter to process the installation and use of the special requirements of environment is not too much, but any kind of flow measurement instrument has such a common, as far as possible to avoid vibration and high temperature environment as flow interference elements (such as compressor, separator, pressure regulating valve, reducer, and pipe, elbow, etc.), keep straight pipe before and after the instrument inside sleek straight, ensure to clean single-phase fluid measured medium, etc.

          Eight, installation requirements:
          1, the sensor can be installed indoors, can also be installed in the outdoor.Environmental conditions to conform to the requirements.
          2, sensors should be installed in a horizontal, vertical or inclined (fluid flow from bottom to top) and its corresponding pipe nominal diameter.
          3, sensors installed on a mechanical vibration of pipeline should be avoided.Should be considered when the vibration is inevitable, at about 2 dn from sensor before and after the straight pipe and fixing racks.
          4, avoid install the sensor sensing has strong electromagnetic interference, thermal radiation, corrosive gas, the space is little, and maintenance is not convenient.
          5, when measured medium contains many impurities, at the request of straight pipe upstream from sensors mounted outside the length of the filter.
          6, either upstream or downstream of the sensor should be configured with a certain length of straight pipe, straight pipe inner surface should be clean, smooth, no obvious convex concave, fouling and peeling phenomenon.Its length should conform to the requirements of figure 2.Installation of the liquid sensor, near the pipe should be filled with liquid to be tested.
          7, straight pipe diameter as far as possible consistent with the sensor size, if not consistent, slightly larger diameter than the sensor size should be adopted, the error to 3% or less is not more than 5 mm.
          Nine, note:
          1, special flange and straight pipe welding can't with the sensor.
          2, when installation should make the flow of sensor mark the direction of flow and the pipe.
          3, before the installation of sensor and the flange must be put away in sealing ring grooves.The location of the pressure and temperature measurement point, pressure downstream of the sensor in 3 ~ 5 dn, temperature measuring points in the downstream of 5 ~ 8 dn.
          4, when measuring high temperature medium, do not use heat insulation material to wrap around the sensor link rod.
          Five, connection of shielded cable, should as far as possible away from the interference of strong electromagnetic field.Absolutely not allowed with high voltage cable laying, shielded cable to shorten as far as possible, and shall not be volume, in order to reduce stray inductance, zui big length should be not more than 200 meters.
          6, before installation of sensors, pipeline cleaning must be conducted.Flow after rinse tube impurities, avoid clogging sensor.Measuring liquid pipe must be full of measured liquid, prevent the interference of bubbles.
          7, measuring gas pipelines to prevent the interference of reservoir fluid.Installation position as shown in figure 5.Replace the probe body under the high temperature and high pressure, it must be safe operation, high temperature protection.After cooling step-down replaceable probe at the bottom of the safety conditions.
          Ten, installation specification management:
          Vortex street flowmeter standard installation, to use the department in the subsequent management provide strong technical support, put forward the following specific requirements of the construction unit, after years of validation effect is very good.
          1, with 4 ~ 20 ma output, pulse output.
          2, GPRS remote transmission device with pulse input, input 4 ~ 20 ma.
          3, with power supply prevents thunder and lightning protection (4 ~ 20 ma) signal.
          4, instrument cabinets for: ark with UPS power supply, open and the socket, the GPRS communication devices, intelligent vortex flowmeter converter such as concentrated installation and lock.
          5, smooth instrument ark need concrete pier base, instrument protection grade for outdoor cabinet, the ark with insulating layer to prevent sun point-blank, ark with water proof function.
          6, domestic demand has left side table well enough straight pipe, facilitate intelligent vortex flowmeter test, compare and follow-up management.
          7, the design of intelligent vortex flow timing front must have at least 10 times of nominal menstruation (dn) 10 straight pipe, the back-end must leave more than 5 dn straight pipe, to ensure accurate measurement.
          8, shall be installed in accordance with the specifications and after the installation need measuring grounding, grounding resistance should be under 10 Ω.Equipotential connections using multiple strands of copper wires, cables should be greater than or equal to 16 was;Instrument grounding line using multiple strands of copper conductor, cable requirement was greater than or equal to 6.Grounding standard see GB50343-2009 "technical specification for building electronic information system lightning protection.

          Eleven, standard of flow range profile: unit (m3 / h)

          traffic 

          The liquid flow range

          Gas flow range

          Saturated steam flow range

          CAL

          Small flow

          Heavy traffic

          Small flow

          Heavy traffic

          Small flow

          Heavy traffic

          DN25

          0.9

          14

          8.3

          110

          13

          1500

          DN40

          2.5

          35

          26

          300

          25

          4400

          DN50

          3.3

          55

          36

          480

          40

          6800

          DN80

          8

          150

          90

          1300

          100

          19000

          DN100

          14

          240

          140

          2000

          160

          29000

          DN150

          38

          450

          290

          4100

          350

          66000

          DN200

          70

          850

          620

          7500

          620

          118000

          DN250

          130

          1300

          700

          12500

          970

          185000

          DN300

          180

          2000

          920

          16500

          1400

          267000

          Twelve, selection of coding:

          Code name

          size

          Flow range ㎡/h(In the wei and control)

          ZW-LUGB-25

          DN25

          1 ~ 10(liquid)

          25 ~ 60(gas)

          Steam flow check specifications,DN300The above recommended plug-in vortex flowmeter

          ZW-LUGB-32

          DN32

          1.5 ~ 18(liquid)

          15-150(gas)

          ZW-LUGB-40

          DN40

          2.2 ~ 27(liquid)

          22.6 ~ 150(gas)

          ZW-LUGB-50

          DN50

          4 ~ 55(liquid)

          35 ~ 350(gas)

          ZW-LUGB-80

          DN80

          9 ~ 135(liquid)

          90 ~ 900(gas)

          ZW-LUGB-100

          DN100

          14 ~ 200(liquid)

          140 ~ 1400(gas)

          ZW-LUGB-150

          DN150

          32 ~ 480(liquid)

          300 ~ 3000(gas)

          ZW-LUGB-200

          DN200

          56-800(liquid)

          550 ~ 5500(gas)

          Code name

          function1

          N

          No temperature pressure compensation

          Y

          With temperature compensation

          Code name

          Output type

          F1

          4-20mAOutput (two-wire system)

          F2

          4-20mAOutput (three-wire system)

          F3

          RS485Communication interface

          Code name

          Measured medium

          J1

          liquid

          J2

          gas

          J3

          steam

          Code name

          The connection method

          L1

          Flange mounted

          L2

          Flange connection type

          Code name

          function2

          E1

          1.0level

          E2

          1.5level

          T1

          The normal temperature

          T2

          The high temperature

          T3

          steam

          P1

          1.6MPa

          P2

          2.5MPa

          P3

          4.0MPa

          W1

          internal3.6VThe power supply

          W2

          DC24VThe power supply

          N1

          Stainless steel

          N2

          Carbon steel

          N3

          Anti-corrosion type

          Thirteen,Order to choose selection guidelines:

          Name and model number of 1, 1), (2) the diameter, flow range, (3) whether or not to bring the attached so that we can correct selection for you, (4) using pressure, (5) the use of medium temperature.

          2, if has been selected by design units in the way of vortex street flowmeter types, please press type vortex flowmeter directly order from our sales department.

          3, when using occasions is very important, or the environment is complex, please try to provide the design drawings and detailed parameters, by wei experts in our audit checks for you.

          After-sales service commitment:

          1, from the date of signing of the contract, I in the way provided for products of the company offers free maintenance and maintenance service, commitment to lifelong maintenance service;

          2, jiangsu wei measurement and control instrument co., LTD. Sales manager will be in regular contact with customers, understand the usage of products, and solve the problems of the customers to use in the process of produce, free of charge to provide technical support;

          3 the man-made damage is found, the warranty period, our company is responsible for the maintenance, and the resulting maintenance fee;

          4, product quality problems or are not satisfied with product, the user can choose unconditional return, wei tt&c don't charge any fees, appear quality problem, bear the freight back and forth.

          Browse:
          Return To The Top

          分(fen)亯(xiang)到(dao):

          RlsnE

            • <b id="6X5oBEp"></b>

                1. <legend></legend>
                  <tr id="6X5oBEp"></tr>